Assessment of microbiological contamination
This research was conducted based on the
European Environmental Protection Agency’s
standard of microbiological pollution (EUR
14988 EN, 1993 [22] as the standard for
assessing the quality of air microbiology in
classrooms. In campus 1, lecture hall I and
room C32 were infested with bacteria and fungi
at a very high level. The bacterial densities
were 1,771.7 CFU/m3 and 1,625.6 CFU/m3
for lecture hall I and room C32, respectively.
The fungal densities were 928.7 CFU/m3
and 729.8 CFU/m3 for lecture hall I and room C32, respectively.
Meanwhile, a considerable extent of contamination in room E401
was observed for bacteria (2,427.3 CFU/m3) and fungi (928.9
CFU/m3) as well. In campus 2, all classrooms had lower levels of
microbiological contamination than campus 1 (Table 2). Bacterial
pollution ranged from an intermediate to high level while fungi
pollution was intermediate. This shows that the microbiological
air quality in campus 1 is inferior to campus 2 and this result is
completely consistent with the results of a study by H. Shokri, et
al. (2010) [30]. Thus, it is necessary to arrange a suitable number
of students for each class, design better ventilation systems, and
clean classrooms regularly to improve air quality in the classrooms.
Identification of microorganisms
The morphological characteristics of the colonies were
selected as a representative of the dominant microorganisms
isolated and identified by the MALDI-TOF method. The results
showed 5 types of bacteria and 3 types of fungi were predominant
over all the sampling sites. The dominant bacteria were Bacillus
atrophaerus, Acinetobacter baumannii, Bacillus pumilus (Fig.
2), Bacillus subtilis, and Bacillus cereus. They were all grampositive bacteria except for Acinetobacter baumannii, which is
gram-negative, and aerobic spores. These bacteria are also found
in soil, water, and some other habitats. Bacillus atrophaerus
is a spore-forming bacillus that does not cause disease. This
bacterium has been used as biological indicators for disinfection
in biological research and method studies as well as in disinfectant
studies, disease treatment evaluation, and potential assistance or
means for vaccines. The remaining types of bacteria are related
to skin diseases, pneumonia, sepsis, incision infection, urinary
tract infection, and purulent meningitis after neurosurgery or
food poisoning [31, 32]. Bacillus pumilus, Bacillus subtilis, and
Bacillus cereus existed at all sampling sites (Table 3) indicating
that they are popular bacteria in indoor air.
The dominant fungi included Aspergillus tamarii, Aspergillus
niger, and Fuligo septica (Fig. 3). Two common fungi of the
genus Aspergillus exist mainly in soil and are associated with
a number of human diseases such as keratitis, allergies, and
rhinitis [33]. They were all present in every classroom except
hall B. Fuligo septica is the culprit of many types of root,
stem, or leaf rot diseases of moistophilic plants, especially
vegetables such as kohlrabi, cabbage, and many other fruits
and vegetables [34]. Fuligo septica only appeared at campus
2 because there are many plants growing on campus (Table 3)
6 trang |
Chia sẻ: hachi492 | Lượt xem: 1 | Lượt tải: 0
Bạn đang xem nội dung tài liệu Microbiological contamination of indoor air in university classrooms (Case study: University of Science - Vietnam National University, Ho Chi Minh city), để tải tài liệu về máy bạn click vào nút DOWNLOAD ở trên
EnvironmEntal SciEncES | Ecology
Vietnam Journal of Science,
Technology and Engineering30 December 2020 • Volume 62 Number 4
Introduction
In recent years, indoor air pollution has been of increasing
interest to scientists as well as environmental management
authorities as most people are indoors about 80-90% of their
time [1, 2]. Hence, indoor air quality is of greater significance
to human health due to the greater exposure time of indoor
air than outdoor air. An average person inhales around
6-10 l/min and needs 15 m3 of air per day [3]; thus, it is
critical that indoor air be studied and evaluated. According
to research by the United States Environmental Protection
Agency (USEPA), indoor air pollution is one of the top
five public health risks [4] contributing to an increase in
the likelihood of cardiovascular diseases, lung diseases, and
respiratory diseases [5].
Research by U.S. scientists (Earth and Sciences Division)
has shown that the air people normally breathe has 1,800
types of bacteria including non-harmful and harmful ones,
both of which affect human health. The human nasal cavity
and the oral cavity contain millions of microorganisms
that are found in indoor air. Some types of bacteria such
as Streptococcus, Mycoplasma, and Staphylococcus cause
skin-related diseases, respiratory system diseases, and
allergies, which leads to an increase in the proportion of
people infected [6, 7]. Human activities, indoor furniture,
and equipment are the main factors contributing to the
accumulation and spread of microbiological contaminants in
indoor air [8, 9]. Human activities such as talking, sneezing,
coughing, walking, and washing can produce biological dust
in the air. Food, houseplants, house dust, clothing, carpets,
wood materials, and furniture can also occasionally release
various types of microorganisms into indoor air. Bacteria
and fungi also come from outdoor sources such as soil or
plants that are transported indoors as dust by wind transport
[10, 11].
An increasing amount of research is also being
Microbiological contamination of indoor air in university classrooms
(Case study: University of Science - Vietnam National University,
Ho Chi Minh city)
Diep Yen Nga Dang*, Hong Nhung Vuong, Thi Tam Nguyen, Thi Thanh Thao Phan
Faculty of Environmental Science, University of Science, Vietnam National University, Ho Chi Minh city
Received 10 August 2020; accepted 9 November 2020
*Corresponding author: Email: ddynga@hcmus.edu.vn
Abstract:
This study was conducted to preliminarily assess
microbial contamination of the indoor air inside
classrooms at the University of Science - Ho Chi Minh
city. At the same time, this study demonstrates the
scientific basis of air quality assessment in a school
environment and develops long-term direct or indirect
solutions to protect the environment and ensure student
health. In this project, sampling and quantitative
analysis were performed to identify the airborne bacteria
and fungi. Samples were collected from classrooms over
a period of 4 months (03-06/2019) according to Koch’s
sedimentation method. The sampling plates were placed
1 m above the floor and the sampling time was 15 min.
The colonies were counted after 24-48 h of incubation
at 37±1oC for the bacteria and 70-120 h at 25±1oC
for moulds. The results showed bacterial and fungal
densities ranging from 359.6-2,427.3 CFU/m3 and
106.1-928.9 CFU/m3, respectively. The bacterial
density was 2-3 times higher than the fungal density
for all survey sites likely because the origin of these
microorganisms is human activity. In addition, the
density of bacteria and fungi in the air were also
affected by weather and environmental factors. 5
isolated bacteria were identified as Bacillus atrophaerus,
Acinetobacter baumannii, Bacillus pumilus, Bacillus
subtilis, and Bacillus cereus. The fungi isolates included
Aspergillus tamarii, Aspergillus niger, and Fuligo septica.
They were all related to human and plant diseases.
Keywords: airborne microorganisms, classroom, indoor
air.
Classification number: 5.1
DOI: 10.31276/VJSTE.62(4).30-35
EnvironmEntal SciEncES | Ecology
Vietnam Journal of Science,
Technology and Engineering 31December 2020 • Volume 62 Number 4
conducted on indoor air bioaerosols. Series of studies on
air microbiology in classrooms, libraries, and lecture halls
of several universities have been carried out. Research
by D. Guan, et al. [12] in China compared the bacterial
density in the classroom between two sampling methods,
of which the density was 209-838 CFU/m3 for the passive
sampling method (Natural sedimentation method - NSM)
and 353-1,932 CFU/m3 for the active sampling method (Air
planktonic bacteria sampling method). In Poland, B. Ewa, et
al. (2018) [13] focused on the viable bacterial concentration
in an office, which was found to be in the range of 540-1,360
CFU/m3. There was a huge difference in bacterial density
between the two types of working rooms, specifically,
the air-conditioned rooms were found to have a bacterial
density 1.5 times higher than non-air-conditioned rooms. In
addition, another study in Ethiopia found that the bacterial
concentrations in some libraries at Jimma University ranged
from 367-2,595 CFU/m3 [14]. It can be easily recognised
that these studies have around a 200-300 CFU/m3 starting
threshold of bacterial density, which is fairly high.
Meanwhile, studies on airborne viable bacteria and
fungi from indoor air have not been paid much attention
in Vietnam. Over the last decade, there have been several
studies on airborne microorganisms in hospitals, food stock,
and outdoor air. N.Q. Tuan (2010) [14] performed some
sampling for a survey of air microbiology in the recovery
and operating rooms of 13 hospitals and found variable
microorganism densities ranging between 64.2-1,247.8
CFU/m3 and higher concentrations obtained at around 200-
500 CFU/m3. The authors referred to the EU clean room
classification standards EU GMP 1997, WHO 2002, and
Merck’s operating room standard (2009) when conducting
this study. At that time, the control of air quality and air
pollution in the hospitals of Vietnam did not have any
standards for the limits of microbiological contamination
in recovery and operating rooms. A study of airborne
microorganisms in food storage warehouses was conducted
by T.N.L. Tuyen, and N.T. Luan (2014) [15] and it showed
that the airborne bacteria concentration was greater than the
concentration of fungi and then proposed safety measures.
In this work, the density of microorganisms in air was
found to decrease from morning to afternoon and increased
from the dry season to the rainy season. The authors
compared the data with the National Technical Regulation
on Biosecurity and Poultry Farm Conditions (QCVN 01-
15:2010/BNNPTNT) and the Safir standard to assess the
aerobic bacteria density in the air because there were no
national regulations on limiting the level of microbiological
contamination in the air for food storage.
In addition, characteristics of airborne bacteria and fungi
in the atmosphere around Ho Chi Minh city from 2014 to
2016 was studied by V.D. Hai, et al. (2019) [16]. There have
been remarkable records of the difference in the number of
microorganisms between inland and suburban locations. The
authors found the average microbial density on weekdays
was higher than on the weekends. This study acknowledged
that Vietnam did not yet have a set of microbiological
standards for the air environment. In addition, the research
had found that passive sampling methods often got higher
density results than active sampling methods. They also
found that the number of airborne microorganisms in the
dry season was usually higher than in the rainy season.
Ho Chi Minh city is the most populous city in Vietnam
and one of the most important economic centres in the
country. This results in a lot of environmental stresses, but,
so far, no research on airborne microorganisms has been
conducted in the classroom of educational institutions. Most
research on the microbiological contamination of indoor and
outdoor air are evaluated based on standards and referenced
standards of countries around the world. At present, there
are not many research papers focusing on environmental
pollution by microorganisms in indoor air.
Therefore, this study provides information on the current
density of bacteria and fungi at several different classrooms
in two campuses of the University of Science, Vietnam
National University, Ho Chi Minh city and the impact of
environmental factors on the growth of microorganisms in
indoor air. The density of microorganisms is one of the most
important criteria to be considered for building a healthy
and safe space for students and teachers.
Methods and materials
Sampling sites
The air samples of the bacteria and fungi were collected
in several classrooms of the University of Science, Vietnam
National University, Ho Chi Minh city. The university has
2 campuses, one in the city centre and one in the suburb of
the city, which has about 20,000 students enrolled. In this
study, the samples were taken from the two campuses at the
following locations. From the first campus, three locations
including room C32 of ~100 students, room E401 of ~50-80
students, and lecture hall 1 of ~300 students. This campus
is near a densely populated area and the main road of the
district (Nguyen Van Cu street, district 5). From the second
campus, room F106 of ~100 students and lecture hall B
of ~300 students. This area is located in the suburbs and
covered with many trees around. There is a long distance
between the blocks of the classrooms (Linh Trung ward,
Thu Duc district).
The different sampling locations provided a variety of
microbial densities in the classrooms of each campus. The
EnvironmEntal SciEncES | Ecology
Vietnam Journal of Science,
Technology and Engineering32 December 2020 • Volume 62 Number 4
criteria for selecting the classroom to be surveyed was to
represent upper and lower floors, the classroom area, and
the number of students in the classroom.
The sample collection time was fixed on the Tuesdays
of each week with 2 weeks per period at the 5 locations
mentioned. There were 4 sampling periods and at each period
samples of bacteria, fungi, and a blank were collected. For
each sampling period, the samples were collected twice per
day at 9:00 and 14:00 for 4 months from March 2019 to
June 2019. Therefore, the total number of expected samples
was 5×4 periods×5 locations=100 samples.
Sampling was conducted by a passive method known
as the natural sedimentation method (NSM) or Koch’s
sedimentation method [17]. The sampling height was
adjusted to be near the human breathing zone, which was
1 m above the floor. Each dish was exposed to air for 15
min (after conducting a pre-survey to select the appropriate
sampling time). During the sampling process, the number of
students, temperature, and humidity for each sampled room
was also recorded.
Sampling procedure
Bacteria and fungi were collected on Nutrient Agar and
Czapek-dox Agar, respectively. After the air exposure, the
plates were carefully packed, labelled, and taken to the
laboratory for analysis of the total aerobic bacteria and total
fungi. The colonies were counted after 24-48 h incubation
at 37±1oC for bacteria and 70-120 h incubation at 25±1oC
for moulds [18]. The samples were finally subjected to
qualitative, quantitative, and microbiological analyses.
Once the colony forming units (CFU) were determined,
the CFU/m3 values were calculated using the following
equation described by Omeliansky [19-21]:
N =
and covered with many trees around. There is a long distance between the blocks of
the classrooms (Linh Trung ward, Thu Duc district).
The different sampling locations provided a variety of microbial densities in the
classrooms of each campus. The criteria for selecting the classroom to be surveyed
was to r present upper and lower fl ors, th classroom area, and the number of
students in the classroom.
The sample collection time as fix d on the Tuesdays of each week with 2
weeks per period at the 5 locations mentioned. There were 4 sampling periods and at
each period samples of bacteria, fungi, and a blank were collected. For each sampling
period, the samples were collected twice per day at 9:00 and 14:00 for 4 months from
March 2019 to June 2019. Therefore, the total number of expected samples was 5×4
periods×5 locations=100 samples.
Sampl ng was conduct d by a passive method known as the natural
sedimentation method (NSM) or Koch's sedimentation method [17]. The sampling
height was adjusted to be near the human breathing zone, which was 1 m above the
floor. Each dish was exposed to air for 15 min (after conducting a pre-survey to select
the appropriate sampling time). During the sampling process, the number of students,
temperature, and humidity for each sampled room was also recorded.
pling procedure
acteria and fungi were collected on Nutrient Agar and Czapek-dox Agar,
respectively. After the air exposure, the plates were carefully packed, labelled, and
taken to the laboratory for analysis of the total aerobic bacteria and total fungi. The
colonies were counted after 24-48 h incubation at 37±1oC for bacteria and 70-120 h
incubation at 25±1oC for moulds [18]. The samples were finally subjected to
qualitative, quantitative, and microbiological analyses.
Once the colony forming units (CFU) were determined, the CFU/m3 values
were calculated using the following equation described by Omeliansky [19-21]:
where N is the microbial counts in CFU/m3 of indoor air, a is the number of colonies
per Petri dish, πr2 is the dish surface area (cm2), and t is the exposure time (min).
The samples of air-borne microorganisms were then compared to the European
Protection Agency's cleanliness classification standards - EUR 14988 EN [22].
This study used protein mass spectrometry (MALDI-TOF) to identify the
microorganisms by molecular markers. Any similarities of protein spectra from the
target microorganisms were determined from a database of nearly 6,000 different
microorganisms. The Maldi biotyper allows the accurate identification of the species
of microorganisms including G(+) and G(–) bacteria, anaerobic–aerobic bacteria, yeast,
mycobacteria, and mycelium. MALDI-TOF is a fast, simple, and high throughput
proteomic technique used to identify many types of bacteria [23].
where N is the microbi ounts in CFU/m3 of indoor air,
a is the number of colonies per Petri dish, πr2 is the dish
surface area (cm2), and t is the exposure time (min).
The samples of air-borne microorganisms were then
compared to the European Protection Agency’s cleanliness
classification standards - EUR 14988 EN [22].
This study used prot in mass spectrometry (MALDI-
TOF) to identify the microorganisms by molecular
markers. Any similarities of protein spectra from the target
microorganisms were determined from a database of nearly
6,000 different microorganisms. The Maldi biotyper allows
the accurate identification of the species of microorganisms
including G(+) and G(–) bacteria, anaerobic-aerobic
bacteria, yeast, mycobacteria, and mycelium. MALDI-TOF
is a fast, simple, and high throughput proteomic technique
used to identify many types of bacteria [23].
Results
The indoor air microbial loads of the 5 classrooms
were determined by taking 100 samples. The concentration
of bacterial and fungi aerosol present in the investigated
classrooms are presented in Table 1. The results indicate
that the highest bacterial air density in CFU/m3 were
obtained at 14:00 h in room E401 at campus 1, while the
lowest bacterial CFU/m3 air values were obtained at 14:00
h in room F106 at campus 2. The highest fungal air values
were recorded at 9:00 h in room E401 at campus 1 with a
value of 928.9 CFU/m3, while the lowest fungal air density
was recorded at 9:00 h in lecture hall B on campus 2, which
was 106.1±81.3 CFU/m3.
Table 1. Number of bacteria and fungi in air (CFU/m3) at 5
points and their sampling time.
Microorganism Sampling time
Campus 1 Campus 2
Lecture hall I
(n=4) Room C32 (n=4) Room E401 (n=4)
Lecture hall B
(n=4)
Room F106
(n=4)
Bacteria
9:00 1,077±854.2 1,598.8±1,958.3 2316±1,826.9 484.7±413.4 785.9±188.1
14:00 1,771.7±776.1 1,625.6±1,285.4 2,427.3±1,906.8 668.1±701.6 359.3±92.4
Fungi
9:00 928.8±398.1 663.5±223.3 928.9±355.3 106.1±81.3 231.5±188.1
14:00 527.5±54.3 729.8±325.1 746.4±627.9 262.6±276.7 121.7±92.4
The bacterial and fungal densities of the 2 campuses are
shown in Fig. 1. The density of microorganisms on campus
1 was higher than that of campus 2 and the bacterial density
was higher than the fungal density.
Fig. 1. Microbiological density in campus 1 and 2.
Microbial air quality scenario of classrooms is indicated
in Table 2. All survey sites were contaminated with micro-
pollutants from low to very high. Room E401 was the most
heavily polluted than the rest of the classrooms.
Results
The indo r air icrobial loads of the 5 classrooms were determined by taking
100 samples. The concentr tion of bacterial and fungi aerosol present in the
investigated classrooms are presented in Table 1. The results indicate that the highest
bacterial air density in CFU/m3 were obtained at 14:00 h in room E401 at campus 1,
while the lowest bacterial CFU/ 3 air values were obtained at 14:00 h in room F106 at
campus 2. The highest fungal air values were recorded at 9:00 h in room E401 at
campus 1 with a value of 928.9 CFU/m3, while the lowest fungal air density was
recorded at 9:00 h in lecture hall B on campus 2, which was 106.1 81.3 CFU/m3.
Table 1. Number of bacteria and fungi in air (CFU/m3) at 5 points and their
sampling time.
Microor
ganism
Sampling
time
Campus 1 Campus 2
Lecture hall
I (n=4)
Room C32
(n=4)
Room E401
(n=4)
Lecture hall B
(n=4)
Room F106
(n=4)
Bacteria
9:00
1,077 854.2 1,598.8 1,958.3 2316 1,826.9 484.7 413.4 785.9 188.1
14:00
1,771.7 776.1 1,625.6 1,285.4 2,427.3 1,906.8 668.1 701.6 359.3 92.4
Fungi
9:00
928.8 398.1 663.5 223.3 928.9 355.3 106.1 81.3 231.5 188.1
14:00
527.5 54.3 729.8 325.1 746.4 627.9 262.6 276.7 121.7 92.4
The bacterial and fungal densities of the 2 campuses are shown in Fig. 1. The
density of microorganisms on campus 1 was higher than that of campus 2 and the
bacterial density was higher than the fungal density.
0
500
1,000
1,500
2,000
2,500
3,000
3,500
9:00 14:00 9:00 14:00
Bacteria Fungi
C
FU
/m
3
The concentration of bacteria and fungi
Campus 1 Campus 2
EnvironmEntal SciEncES | Ecology
Vietnam Journal of Science,
Technology and Engineering 33December 2020 • Volume 62 Number 4
As seen in Table 3, the microbial isolates included 5 bacteria
and three fungi. Bacillus pumilus, Bacillus subtilis, and Bacillus
cereus are common bacteria in the indoor air. They were present
across all sampling locations. Aspergillus tamarii and Aspergillus
niger were two common fungi appearing in all classrooms except
lecture hall B.
Table 3. The distribution of microorganisms.
Microorganism
Campus 1 Campus 2
Lecture
hall I
Room
C32
Room
E401
Lecture
hall B
Room
F106
Bacteria
Bacillus atrophaerus + − − + +
Acinetobacter baumannii − − + + −
Bacillus pumilus + + + + +
Bacillus subtilis + + + + +
Bacillus cereus + + + + +
Fungi
Aspergillus tamarii + + + + +
Aspergillus niger + + + − +
Fuligo septica − − − + +
(+) exist; (−) does not exist.
Discussion
Microbiological analysis
The concentration of bacteria in the classrooms of the two
campuses ranged from 359.6±92.4 CFU/m3 to 2,427.3±1,906.8
CFU/m3 and tended to increase as morning progressed to afternoon.
In campus 1, the average bacterial concentration in the room E401
was the highest during the survey and the lowest concentration in
lecture hall I with 1,077±854.2 CFU/m3. Meanwhile in campus
2, the bacterial density in hall B and room F106 tended to be
opposite in the morning and afternoon (Table 1). This is mainly
explained by the fixed schedule of the week, the same number of
students during the sampling period, the area of the classroom and
the ventilation, outside air entering the classrooms (temperature,
humidity) [24, 25]. Room E401 is small and has poor ventilation
but the number of students in class is about 100. The remaining
rooms have the same area, which is double the size of the E401
room, so the collected bacterial density was lower. A 2012 study
by D. Hospodsky, et al. [26] in the United States also showed
that the bacteria present in indoor air were derived primarily
from humans. Therefore, the number of occupants in an indoor
environment greatly affects the density of the bacteria in the air.
Similar to bacteria, the concentration of fungi at campus
1 was lowest at 527.5±54.3 CFU/m3 in lecture hall I and the
highest concentration was 928.9±355.3 CFU/m3 in room E401.
This was significantly different from the concentration values
found at campus 2, which ranged only from 106.1±81.3 CFU/m3
to 262.6±276.7 CFU/m3. However, the difference in fungal
density among the classrooms in each campus was quite small,
only about 200 CFU/m3 at campus 1 and 120 CFU/m3 at campus
2 (Table 1). This shows that people are not the main source of
fungi in the indoor air. The room’s facilities, high humidity, and
poor cleanliness of the rooms are conditions that support the strong
growth of fungi. Correlation studies of microorganisms inside
buildings were conducted by S.A. Wamedo, et al. (2012) [25]
and G.S. Graudenz, et al. (2005) [27], which were in agreement
with this view. The concentration of fungi in the morning tended
to be higher than in the afternoon because the temperature in the
morning was around 30oC, which is suitable for fungi growth [28].
From the data in Table 1, the bacterial density was 2-3
times higher than the fungal density at all survey locations. The
temperature in Ho Chi Minh city is quite high (32-37oC) during the
days, which is more suitable for the growth of bacteria rather than
fungi (the optimal temperature range of fungi is 28-30oC) [16]. In
summary, the origin of bacteria in the indoor air is mainly from
humans while the origin of the fungi is from the condition of the
facilities as well as environmental factors. Samples collected in
this study were themselves the cause of large density difference
between bacteria and fungi concentration [24].
The concentration of microorganisms between 2 campuses
The concentrations of bacteria and fungi were found to be
significantly different between the sampling locations of both
campuses. Fig. 1 shows that the average density of bacteria at
Table 2. Evaluation of microbiological air quality (According to the standards of the European Protection Agency - EUR 14988 EN,
1993 [22]).
Microorganism Range of values (CFU/m3)
Pollution
degree
Campus 1 Campus 2
Lecture hall I Room C32 Room E401 Lecture hall B Room F106
9:00 14:00 9:00 14:00 9:00 14:00 9:00 14:00 9:00 14:00
Bacteria
<50 Very low − − − − − − − − − −
50-100 Low − − − − − − − − − −
100-500 Intermediate − − − − − − − −
500-2,000 High − − − −
>2,000 Very high − − − − − − − −
Fungi
<25 Very low − − − − − − − − − −
25-100 Low − − − − − − − − − −
100-500 Intermediate − − − − − −
500-2,000 High − − − −
>2,000 Very high − − − − − − − − − −
() in the range; (−) not in the range.
EnvironmEntal SciEncES | Ecology
Vietnam Journal of Science,
Technology and Engineering34 December 2020 • Volume 62 Number 4
campus 1 in the morning and afternoon was 2-3 times higher than
that of campus 2. The bacterial concentration in the afternoon
was the highest at 1,941.5 CFU/m3 while the highest bacterial
concentration in campus 2 was only 635.3 CFU/m3. Similarly, the
highest fungal density was 840.4 CFU/m3 at campus 1, which is
4-5 times higher when compared with campus 2. One explanation
for this result is that campus 1 in the city centre where many high-
rise buildings are situated nearby. The area of campus 1 is small
and the natural ventilation in classrooms (they are without air-
conditioners) is not good, which leads to high humidity. The roads
in this area are less green and contain a high density of vehicles
that generate dust suspended in the air, which easily attaches to
the human body. At the same time, the number of students at this
facility is quite large, so the air quality in the poorly-ventilated
classrooms are worse. campus 2 is located on the outskirts of
the city with greener roads and its area is three times larger than
campus 1. However, campus 2 is located apart from major road
systems and as a result there is less traffic on the roads. The class
sizes of campus 2 are much less than the capacity of the classroom,
which results in less dust-containing microorganisms. Research by
W. Fabian, et al. (2016) [29] also has stated that environmental
and outdoor factors (vegetation, urbanization, airborne particulate
matter) affect the growth of mould and bacteria in the indoor air.
Assessment of microbiological contamination
This research was conducted based on the
European Environmental Protection Agency’s
standard of microbiological pollution (EUR
14988 EN, 1993 [22] as the standard for
assessing the quality of air microbiology in
classrooms. In campus 1, lecture hall I and
room C32 were infested with bacteria and fungi
at a very high level. The bacterial densities
were 1,771.7 CFU/m3 and 1,625.6 CFU/m3
for lecture hall I and room C32, respectively.
The fungal densities were 928.7 CFU/m3
and 729.8 CFU/m3 for lecture hall I and room C32, respectively.
Meanwhile, a considerable extent of contamination in room E401
was observed for bacteria (2,427.3 CFU/m3) and fungi (928.9
CFU/m3) as well. In campus 2, all classrooms had lower levels of
microbiological contamination than campus 1 (Table 2). Bacterial
pollution ranged from an intermediate to high level while fungi
pollution was intermediate. This shows that the microbiological
air quality in campus 1 is inferior to campus 2 and this result is
completely consistent with the results of a study by H. Shokri, et
al. (2010) [30]. Thus, it is necessary to arrange a suitable number
of students for each class, design better ventilation systems, and
clean classrooms regularly to improve air quality in the classrooms.
Identification of microorganisms
The morphological characteristics of the colonies were
selected as a representative of the dominant microorganisms
isolated and identified by the MALDI-TOF method. The results
showed 5 types of bacteria and 3 types of fungi were predominant
over all the sampling sites. The dominant bacteria were Bacillus
atrophaerus, Acinetobacter baumannii, Bacillus pumilus (Fig.
2), Bacillus subtilis, and Bacillus cereus. They were all gram-
positive bacteria except for Acinetobacter baumannii, which is
gram-negative, and aerobic spores. These bacteria are also found
in soil, water, and some other habitats. Bacillus atrophaerus
is a spore-forming bacillus that does not cause disease. This
bacterium has been used as biological indicators for disinfection
in biological research and method studies as well as in disinfectant
studies, disease treatment evaluation, and potential assistance or
means for vaccines. The remaining types of bacteria are related
to skin diseases, pneumonia, sepsis, incision infection, urinary
tract infection, and purulent meningitis after neurosurgery or
food poisoning [31, 32]. Bacillus pumilus, Bacillus subtilis, and
Bacillus cereus existed at all sampling sites (Table 3) indicating
that they are popular bacteria in indoor air.
The dominant fungi included Aspergillus tamarii, Aspergillus
niger, and Fuligo septica (Fig. 3). Two common fungi of the
genus Aspergillus exist mainly in soil and are associated with
a number of human diseases such as keratitis, allergies, and
rhinitis [33]. They were all present in every classroom except
hall B. Fuligo septica is the culprit of many types of root,
stem, or leaf rot diseases of moistophilic plants, especially
vegetables such as kohlrabi, cabbage, and many other fruits
and vegetables [34]. Fuligo septica only appeared at campus
2 because there are many plants growing on campus (Table 3).
Conclusions
This study has provided important information on the status
of microorganisms in the air and a preliminary evaluation of the
microbiological air quality in indoor air at schools. Along with
identifying the species, this study helped elucidate the impacts from
these microorganisms in the air. The concentrations of bacteria in
the air depend on factors such as weather, ventilation, as well as
human activities. A limited classroom area with crowded human
presence has a strong impact on the density and concentrations
of bacteria in the air, which causes them to be high. The fungi
concentration depends on environmental factors, the quality of
facilities, and sanitation in the classroom. The inferior air quality
of campus 1 compared to campus 2 is likely caused by differences
of geographical locations. The classrooms at campus 1 have high-
to-very high microbiological pollution while campus 2 has an
average pollution level. To improve air quality, it is necessary to
arrange a suitable number of students for each class, appropriately
design ventilation, and to clean the classrooms regularly.
Fig. 2. Bacillus pumilus bacteria before
and after isolation.
Fig. 3. Types of fungi under microscope.
for lecture hall I and room C32, respectively. Meanwhile, a considerable extent of
contamination in room E401 was observed for bacteria (2,427.3 CFU/m3) and fungi
(928.9 CFU/m3) as well. In campus 2, all classrooms had lower levels of
microbiological contamination than campus 1 (Table 2). Bacterial pollution ranged
from an intermediate to high level while fungi pollution was intermediate. This shows
that the microbiological air quality in campus 1 is inferior to campus 2 and this result
is completely consistent with the results of a study by Shokri, et al. (2010) [30]. Thus,
t is necessary to arrange s itable um er of students for each class, design better
ventilation systems, and clean classrooms regularly to improve air quality in the
classrooms.
Identification of microorganisms
The morphological characteristics of the colonies were selected as a
represent tive of the dominant microorganisms isol te and identified by the MALDI-
TOF method. The results showed 5 types of bacteria and 3 types of fungi were
predominant over all the sampling sites. The dominant bacteria were Bacillus
atrophaerus, Acinetobacter baumannii, Bacillus pumilus (Fig. 2), Bacillus subtilis, and
Bacillus cereus. They were all gram-positive bacteria except for Acinetobacter
baumannii, which is gram-negative, and aerobic spores. These bacteria are also found
in soil, water, and some other habitats. Bacillus atrophaerus is a spore-forming
bacillus that d es not caus disease. This bac erium has been us d a biological
indicators for disinfection in biological research and method studies as well as in
disinfectant studies, disease treatment evaluation, and potential assistance or means for
vaccines. The remaining types of bacteria are related to skin diseases, pneumonia,
sepsis, incision infection, urinary tract infection, and purulent meningitis after
neurosurgery or food poisoning [31, 32]. Bacillus pumilus, Bacillus subtilis, and
Bacillus cereus existed at all sampling sites (Table 3) indicating that they are popular
bacteria in indoor air.
The do inant fungi included Aspergillus tamarii, Aspergillus Niger, and Fuligo
septica (Fig. 3). Two common fungi of the genus Aspergillus exist mainly in soil and
are associat d with a number of human diseases such as keratitis, allergies, and rhinitis
[33]. They were all present in every classroom except hall B. Fuligo septica is the
culprit of many types of root, stem, or leaf r t diseases of moistophilic plants,
especially vegetables such as kohlrabi, cabbage, and many other fruits and vegetables
[34]. Fuligo septica only appeared at campus 2 because there are many plants growing
on campus (Table 3).
Fuligo septica Aspergillus tamarii
ig. . l s ilus acteria
before and after isolation.
Bacillus pumilus
Aspergillus Niger
Fig. 3. Types of fungi under microscope.
EnvironmEntal SciEncES | Ecology
Vietnam Journal of Science,
Technology and Engineering 35December 2020 • Volume 62 Number 4
ACKNOWLEDGEMENTS
The authors would like to thank the lecturers of the Faculty
of Environment, University of Science - Ho Chi Minh city
for their support of facilities, technical expertise and the best
conditions for the authors completed this research topic.
COMPETING INTERESTS
The authors declare that there is no conflict of interest
regarding the publication of this article.
REFERENCES
[1] A.H. Awad, S.A. Farag (1999), “An indoor bio-contaminants air quality”,
International Journal of Environmental Health Research, 9(4), pp.313-319, DOI:
10.1080/09603129973100.
[2] T. Lind, Nilssonmam, T. Bellander, J. Wichmann (2010), “PM2.5, soot and
NO2 indoor-outdoor relationships at home, pre-school and schools in Stockholm,
Sweden”, Atmospheric Environment, 44(36), pp.4536-4544, DOI: 10.1016/j.
atmosenv.2010.08.023.
[3] R.A. Wood, R.A. Burchett, J.T. Orwell, F.R. Torpy (2002), Plant/Soil
Capacities to Remove Harmful Substances from Polluted Indoor Air, Plants and
Environmental Quality Group, Centre for Ecotoxicology, UTS.
[4] H. Gawronska, B. Bakera (2015), “Phytoremediation of particulate
matter from indoor air by Chlorophytum comosum L. plants”, Air Qual. Atmos.
Health, 8, pp.265-272, DOI: 10.1007/s11869-014-0285-4.
[5] S.K. Shin, J. Kim, S. Ha, H.S. Oh, J. Chun, J. Sohn, Y. Hana (2015),
“Metagenomic insights into the bioaerosols in the indoor and outdoor environments
of childcare facilities”, PLOS ONE, 10(5), pp.1-17, DOI: 10.1371/journal.
pone.0126960.
[6] P. Treebupachatsakul, S. Tiengrim, V. Thamlikitkul (2006), “Upper
respiratory tract infection in Thai adults: prevalence and prediction of bacterial
causes and effectiveness of using clinical practice guidelines”, Journal of the Medical
Association of Thailand, 89(8), pp.1178-1186.
[7] W. Heping, et al. (2016), “Mycoplasma pneumoniae and streptococcus
pneumoniae caused different microbial structure and correlation network in lung
microbiota”, Journal of Thoracic Diseaes, 8(6), pp.1316-1322.
[8] J. Qian, D. Hospodsky, N. Yamamoto, W. Nazaroff, J. Peccia (2015), “Size-
resolved emission rates of airborne bacteria and outdoor environments of childcare
facilities”, PLOS ONE, 10, pp.1-17.
[9] M. Taubel, H. Rintala, M. Pitkaranta, L. Paulin, S. Laitinen, J. Pekkannen
(2009), “The occupant as a source of house dust bacteria”, J. Allergy Clin. Immunol.,
124, pp.834-840.
[10] M.D. Giulio, R. Grande, E.D. Campli (2010), “Indoor air quality in
university environments”, Environ. Monit. Assess., 170(1-4), pp.509-517, DOI:
10.1007/s10661-009-1252-7.
[11] W.W. Nazaroff (2016), “Indoor bioaerosol dynamics”, Indoor Air, 26,
pp.61-78, DOI: 10.1111/ina.12174.
[12] D. Guan, C. Gou, Y. Li, H. Lv, X. Yu (2015), “Study on the concentration
and distribution of the airborne bacteria in indoor air in the lecture threatres at Tianjin
Chengjian University, China”, Procedia Engineering, 121, pp.33-36, DOI: 10.1016/j.
proeng.2015.08.1015.
[13] B. Ewa, B. Izabela, K. Barbara, S.P. Jozef (2018), “Microbiological indoor
air quality in an office building in Gliwice, Poland: analysis of the case study”, Air
Quality, Atmosphere & Heatlh, 11, pp.729-740, DOI: 10.1007/s11869-018-0579-z.
[14] N.Q. Tuan (2010), “Survey of microbiological pollution in the air of
operating and recovery rooms in some hospitals in Ho Chi Minh city”, Medical
Research, 14, pp.173-179.
[15] T.N.L. Tuyen, N.T. Luan (2014), Study the Situation of Microbiological
Pollution in the Air in Food and Food Industry Storage and Propose Safety Measures
for Humans and Raw Materials, Center for the Development of Science and
Technology Young, Ho Chi Minh city, pp.4-26.
[16] V.D. Hai, S.M.T. Hoang, N.T.Q. Hung, N.M. Ky, S. Nam, V.B. Quang,
T.T.N. Trang, N.D. Duc (2019), “Characteristics of airborne bacteria and fungi in the
atmosphere in Ho Chi Minh city, Vietnam - a case study over three years”, International
Biodeteioration and Biodegradation, 145, DOI: 10.1016/j.ibiod.2019.104819.
[17] P.H. Arthur, C.L. Morris (1939), “The introduction of agar-agar into
bacteriology”, Journal of Bacteriol, 37(5), pp.485-493, DOI: 10.1128/JB.37.5.485-
493.1939.
[18] P.G. Martin (1997), “Quality assurance in the food control microbiological
laboratory”, Manual of Food Quality Control, Food and Agriculture Organization of
the United Nations Rome.
[19] F.H. Samuel, M.M. Abayneh (2014), “Microbiological quality of indoor
air in university libraries”, Asian Pac. J. Trop. Biomed., 4(1), pp.312-317, DOI:
10.12980/APJTB.4.2014C807.
[20] S. Borrego, et al. (2010), “The quality of air at archives and the
biodeterioration of photographs”, Int. Biodeterior. Biodegradation, 64(2), pp.139-
145, DOI: 10.1016/j.ibiod.2009.12.005.
[21] B. Gutarowska (2010), “Metabolic activity of moulds as factor of building
materials biodegradation”, Polish Journal of Microbiology, 59(2), pp.119-124.
[22]
[23] A.E. Clark, E.J. Kaleta, A. Arora, D.M. Wolk (2013), “Matrix-assisted laser
desorption ionization-time of flight mass spectrometry: a fundamental shift in the
routine practice of clinical microbiology”, Clin. Microbiol. Rev., 26(3), pp.547-603,
DOI: 10.1128/CMR.00072-12.
[24] J.F. Meadow, et al. (2014), “Indoor airborne bacterial communities are
influenced by ventilation, occupancy and outdoor air source”, Indoor Air, 24(1),
pp.41-48, DOI: 10.1111/ina.12047.
[25] S.A. Wamedo, P.N. Ede, K. Chuku (2012), “Interaction between building
design and indoor airborne microbial load in Nigeria”, Asian J. Biol. Sci., 5(4),
pp.183-191, DOI: 10.3923/ajbs.2012.183.191.
[26] D. Hospodsky, et al. (2012), “Human occupancy as a source of indoor
airborne bacteria”, PLOS ONE, 7(4), DOI: 10.1371/journal.pone.0034867.
[27] G.S. Graudenz, C.H. Oliveira, A. Tribess, C. Mendes, M.R. Latorre, J.
Kalil (2005), “Association of air-conditioning with respiratory symptoms in office
workers in tropical climate”, Indoor Air, 15(1), pp.62-66, DOI: 10.1111/j.1600-
0668.2004.00324.x.
[28] A.A. Komlavi (2015), Fungal Aerosols: Characterization and
Immunodetection of Fungal Fragments, Philosophiae Doctor (PhD) Thesis,
Norwegian University of Life Sciences.
[29] W. Fabian, et al. (2016), “Fungal and bacterial communities in indoor dust
follow different environmental determinants”, PLOS ONE, 11(4), e0154131pp, DOI:
10.1371/journal.pone.0154131.
[30] H. Shokri, et al. (2010), “Common environmental allergenic fungi causing
respiratory allergy in North of Iran”, International Journal of Veterinary Research,
4(3), pp.169-172, DOI: 10.22059/IJVM.2010.21348.
[31] Morbidity and Mortality Weekly Report (2005), Outbreak of Cutaneous
Bacillus Cereus Infection among Cadets in a University Military Program, Centers
for Disease Control and Prevention, Georgia, 54(48), pp.1233-1235.
[32] T.L. Pitt, et al. (2007), “Characterisation of Exiguobacterium aurantiacum
isolates from blood cultures od six patients”, Clinical Microbiology and Infection,
13(9), pp.946-948, DOI: 10.1111/j.1469-0691.2007.01779.x.
[33] W.T.T. Emily, et al. (2014), “Misidentification of aspergillus nomius and
aspergillus tamarii as aspergillus flavus: characterization by internal transcribed
spacer, β-tubulin, and calmodulin gene sequencing, metabolic fingerprinting, and
matrix-assisted laser desorption ionization-ti”, Journal of Clinical Microbiology,
52(4), pp.1153-1160, DOI: 10.1128/JCM.03258-13.
[34] K. Anna, P. Alzbieta, M. Dominika, P. Przemyslaw (2008), “Sclerotia of
the acellular (true) slime mould Fuligo septica as a model to study melanization
and anabiosis”, Cellular and Molecular Biology Letters, 13(1), pp.130-143, DOI:
10.2478/s11658-007-0047-5.
Các file đính kèm theo tài liệu này:
microbiological_contamination_of_indoor_air_in_university_cl.pdf