This paper provides a detailed description of a
transformer different protection function based on a
two-slope characteristic. It also provides valuable tips on
how to guide the setting calculation and troubleshooting
process. Furthermore, the power system model simulates
numerous test cases for an existing power transformer of
Lang Co Substation, Viet Nam using Matlab/Simulink
software package. These test cases save time by
immediately indicating whether the issue has occurred on
the SEL387. As a result, protection engineers can easily
analyze the mis-operation to determine the root cause and
can fulfill very demanding requirements set by power
utilities.
5 trang |
Chia sẻ: huongthu9 | Lượt xem: 551 | Lượt tải: 0
Bạn đang xem nội dung tài liệu Performance analysis and assessment of a transformer different protection relay sel387 at 110kv lang co substation, để tải tài liệu về máy bạn click vào nút DOWNLOAD ở trên
8 Le Kim Hung, Vu Phan Huan
PERFORMANCE ANALYSIS AND ASSESSMENT OF A TRANSFORMER
DIFFERENT PROTECTION RELAY SEL387 AT 110KV LANG CO SUBSTATION
Le Kim Hung1, Vu Phan Huan2
1University of Science and Technology – The University of Danang; lekimhung@dut.udn.vn
2Center Electrical Testing Company Limited; vuphanhuan@gmail.com
Abstract - Based on the influences of current transformer
connection type, CT errors, magnetizing inrush current, errors
because of tap changing and fault conditions on differential
protection function, the paper establishes and assesses the
performance of a numerical relay SEL387 model concerning the
protection of the 115/24kV transformer at Lang Co Substation by
Matlab/Simulink. The paper also calculates the setting value of two
actual slope characteristics (O87P = 0.3, U87P = 10, SLP1 = 25%,
SLP2 = 50% and IRS1 = 3). The results can be applied to increase
the accurate and reliable performance of the differential
transformer protection relay against internal faults. Simulation has
simplified the process of selecting relay and protection system.
This can improve the quality of the protection system design early,
thereby reducing the number of errors found later in the operation.
Key words - Different protection relay; transformer; two slope
characteristics; Matlab/Simulink; SEL387.
1. Introduction
Nowadays, there are a variety of numerical transformer
different protective relays on the market such as Siemens
7UT613, SEL387, Schneider P632, Toshiba GRT200,
ABB RET670, which include many functions in one unit,
as well as providing metering, communication, and
transformer protection. These protective relays help us to
simplify implementation of the protection in circuit design
and setting calculations.
The connection diagram is used for the numerical
protective relay SEL387 (shown in Figure 1) that provides
protection of two transformer windings (HV, LV) as well
as differential function (F87T) for sensitive detection of
inter turn faults within the transformer winding. Both HV
CTs and LV CTs are wye connected. The F87T obtains
three phase current inputs from them. This function
compares the currents entering and leaving the protected
zone of the windings of the transformer.
Figure 1. Secondary current in HV and
LV side at normal condition
As with most false trips involving F87T in Central
Power Grid, checking the relay should be done first, and
can be done by inspecting the LED indicators, cable
connections, auxiliary relay and so on. The main cause
shown in Figure 2 is CT secondary wire connected to the
incorrect tap on the CT, Crossed phases, Incorrect CT
polarity in design or construction [2]. In addition, there is a
general lack of understanding the ground differential
protection principle. In most cases, inadequate or no
verification test is performed to check the correctness of the
secondary current circuit. So, these errors depend on skill of
testers. If the hardware has no issues, then it is very likely to
be a setting problem. Unlike hardware issues, setting issues
cannot be assessed by the naked eyes, so the universal relay
test set and commissioning tool are required. It performs to
check wiring and setting of relays, by using
primary/secondary injection of currents from the test set.
Figure 2. Incorrect CT Ratio, CT Polarity, or Crossed Phases
But even in a no fault situation, the magnitude and the
phase of the currents in both sides of the transformer will
not have the same value. This is often the case that mis-
operation on relay does not become apparent immediately.
One possibility is CT errors, magnetizing inrush current
during initial energization, CTs mismatch and saturation.
Another possibility is that the transformation ratio changes
due to Tap changer. These have already been introduced to
the different currents by devices that have not yet caused
any problems, but will cause significant disruption to the
transformer in the future. Besides, the possibility is that
someone with unauthorized access infiltrates the relay and
reconfigures incorrect setting to a relay, instructing it to
release a false trip signal without the existence of any fault.
When these types of mis-operation risks go undetected, it
is very easy for substation operators to mistakenly believe
that their relay protection is secure. The question substation
operators need to ask is, “How confident am I that my relay
protection is reliable and secure?”
After this introduction, the rest of the paper is organized
as follows. The section 2 describes the transformer
different protection function and provides instructions for
setting calculation SEL387 in Lang Co substation. The
section 3 builds the power system and the relay protection
on Matlab Simulink. The section 4 simulates the testing
normal/fault conditions. The section 5 gives the
conclusions related to the transformer different protection.
ISSN 1859-1531 - THE UNIVERSITY OF DANANG, JOURNAL OF SCIENCE AND TECHNOLOGY, NO. 6(127).2018 9
2. Transformer different protection function
The main operation of a current differential protection
relay is made by comparing the vector current in both sides
of the transformer: IDIFF = |I1 + I2| (1)
Restraint current:
IBIAS = |I1| + |I2| (Siemens, Sel, Abb) (2)
IBIAS = 0.5(|I1| + |I2|) (Schneider) (3)
a. Siemens 7UT613 characteristic b. SEL387 characteristic
c. ABB RET670 characteristic d. Schneider P632 characteristic
Figure 3. Differential protection characteristic
Based on these values of IBIAS and values of IDIFF, the
trip/restrain characteristics offer from vendors of
protection relay such as Siemens, Sel, Abb, and Schneider
which has a three-step shape (two slopes and one pickup
level) as in Figure 3 and defined by the following settings
as in Table 1. The F87T operates when IDIFF exceeds a
minimum operate current threshold and a percentage of
IBIAS, defined by a slope setting (slope 1, slope 2). Consider
matlab code of this matter in subsection 3 below.
Table 1. Parameter characteristic of relay vendors
Parameter Siemens Sel Abb Schneider
Minimum
pickup
IDIFF> 87OP Idmin IS1
Slope 1 Slope 1 Slope 1 Slope Section 2 K1
Slope 2 Slope 2 Slope 2 Slope Section 3 K2
Unrestraint
tripping
IDIFF>> 87UP ID>>
Points of
intersection
Base Point 2 IRS1
End Section1,
End Section 2
IS2
To help us understand a setting calculation for relays,
we use SEL 387 to protect a 25MVA, 50Hz, (115/24) kV,
Y/y0 Vina Takaoka transformer in Lang Co Substation that
has CTHV = 200/1, CTLV = 800/1, and an OLTC with
tapping range from 1 to 19 positions. It has satisfied the
following requirements from Decision No. A3-06-
2015/LCO110 by the Central Region Load Dispatch
Centre of Vietnam [3, 6].
Windings 1 and 3 are validated for differential
protection. Settings will be: E87W1 = Y, E87W3 = Y.
The voltages for winding 1 and 3 are 115kV and 24kV,
respectively: VWDG1 = 115, VWDG3 = 24.
The internal compensation (ICOM = Y) for the
wye-wye transformer with a wye-wye CT can be set to
12 to remove the zero sequence currents.
Winding 1 CT Conn.Compensation W1CTC =12
Winding 3 CT Conn.Compensation W3CTC =12
The following settings refer to the CTs connection and
to the current ratio for each winding: W1CT = Y;
CTR1 =200; W3CT = Y; CTR3 = 800.
The secondary current of CT HV side under normal
operating condition is:
IHV = MVA/(1.732 × VWDG1× CTR1)
IHV = 25×106/(1.732×115×103×200) = 0.628 [A]
and requires ratio compensation TAP1 = 1/0.628 = 1.593
Under normal condition, secondary current in LV side is:
ILV = MVA/(1.732 ×VWDG3×CTR3)
ILV = 25×106/(1.732×24×103×800) = 0.752 [A]
and requires ratio compensation TAP3 = 1/0.752 = 1.33
a. Setting characteristic b. Test point in
Normal/ Fault conditions
Figure 4. SEL 387 setting characteristic in Lang Co Substation
As shown in Figure 4a, dual slope characteristics can
be used with a minimum pickup setting. This can be
mathematically represented as follows:
The minimum pickup O87P should be set as sensitively
as possible while considering the steady state CT error and
transformer magnetizing current. The O87P setting must
yield an operating current value of at least 0.1×IN, at the
least tap. In this case O87P ≥ 0.1IN/TAPMIN = 0.1x1/
1.33 = 0.0752. The typical O87P range is 0.3 to 0.5.
Therefore, the O87P setting of 0.3 is valid.
The instantaneous unrestrained current element is
intended to react quickly to very heavy current levels that
clearly indicate an internal fault. Set the pickup level (U87P)
about 10 times TAP. The unrestrained differential element
only responds to the fundamental frequency component of the
differential operating current. It is not affected by the SLP1,
SLP2, IRS1, PCT2, PCT5, or IHBL settings. Thus, it must be
set high enough so as not to react to large inrush currents.
Slope 1 region is used between the minimum pickup
region and the slope 2 breakpoint. Slope 1 provides
security against false tripping due to the following factors:
Excitation current = 2 %, CT accuracy = 3%, NLTC = 5%,
LTC = 10%, Tap mismatch = 0%, and Relay
accuracy = 5%. All these percentages sum to 25 %, thus a
setting of SLP1 = 25% can be used.
IDIFF/IN
IBIAS/IN
Idmin
End Section 1
Slope Section 2
End Section 2
Slope Section 3
IDIFF/IN
IBIAS/IN
I
K1
IS2
K2
TAP Pos is 18
IDIFF/IN
IBIAS/IN
O87P
IRS1
CT Error
U87P
TAP Pos is 9
External Fault
Internal Fault
Magnetization
SLP1 = 0.25
SLP2 = 0.5
IDIFF/IN
IBIAS/IN
O87P
Sum
IRS1 = 3
Saturation
TAP
changer
U87P
10 Le Kim Hung, Vu Phan Huan
Slope 2 is used to prevent false tripping caused by
saturation of the CTs. A setting of SLP2 = 50 % for slope
2 covers all the situation.
IRS1 = 3 is restraint current slope 1 limit.
Operate time (restrained function): 20 to 35 ms.
Operate time (unrestrained function): 5 to 20 ms.
PCT2 = 15% (the F87T is going to be blocked if the
second harmonic is higher than 15% from fundamental).
PCT5 = 35% (the F87T is going to be blocked if the
fifth harmonic is higher than 35% from fundamental) and
TH5P = OFF (the 5th harmonic alarm is deactivated).
3. Building of the differential protection function using
Matlab Simulink
For the purpose of testing reliability of the relay
protection from SEL vendor to test the algorithm of
different protection, the power system model has been
simulated in the Matlab Simulink and it is depicted in
Figure 5. It consists of a 115 kV, 1000 MVA system, a
25MVA, 50Hz, (115/24) kV, Y/y0 OLTC regulating
transformer, two CT (200/1A and 800/1A), 24 MW /1Mvar
loading and SEL 387 relay protection. All fault conditions
are created to transformer via the three phase fault block.
A relay SEL387 model shown in Figure 6 combines
functions of vector group compensation, TAP factor
compensation, different and bias current calculation,
inrush harmonic blocking and slope characteristics. Firstly,
current signals have been simulated in Matlab, which
combines vector group value of current throw S-function,
which is used to correct the phase shift across the YNy0
transformer. Since the HV, LV side of the transformer are
wye connected, they require and will use the same Ɵ = 00.
The identity matrix is shown below:
)cos()120cos()120cos(
)120cos()cos()120cos(
)120cos()120cos()cos(
3
2
)(0
00
00
00
−+
+−
−+
=CTC
C
B
A
C
B
A
COMPC
COMPB
COMPA
I
I
I
I
I
I
CTC
I
I
I
−−
−−
−−
==
211
121
112
3
1
)0(0 0
_
_
_
After that it sends to the subsystem combined TAP
factor compensation (TAP1 = 1.59, TAP3 = 1.32).
Secondly, the subsystem different value and bias of current
are calculated for each phase separately according to the
relation of the equation (1) and (2). Similarly, in the
harmonic subsystem the F87T is going to be blocked if the
second harmonic is higher than 15% from fundamental.
Finally, S-Function Builder checks the position of operating
point described by currents (for each phase separately) with
respect to the pick-up characteristic IDIFF = f(IBIAS) and
decision tripping the pulse, which opens a circuit breakers
located on both sides of the protected transformer. The
following Matlab code is written for phase A:
Figure 5. Matlab/Simulink Model of the proposed system
Figure 6. Overview of the function blocks of the F87T
ISSN 1859-1531 - THE UNIVERSITY OF DANANG, JOURNAL OF SCIENCE AND TECHNOLOGY, NO. 6(127).2018 11
double IRT = (*O87P) / (*SLP1);/* starting point of
SLP1*/
double IRT2 = (*U87P) / (*SLP2); /* ending point of
SLP2*/
if ((*Ibias_A <= IRT) && (*Harmonic_Block == 0))
{
if (*Idiff_A > (*O87P))
*Output = 1;
else
*Output=0;
}
else
{
if (*Idiff_A > (*U87P))
*Output = 1;
else
*Output=0;
}
if ((*Ibias_A > IRT) && (*Ibias_A <= *IRS1) &&
(*Harmonic_Block == 0))
{
if (*Idiff_A > ((*Ibias_A) * (*SLP1)))
*Output = 1;
else
*Output=0;
}
if ((*Ibias_A > *IRS1) && (*Ibias_A <= IRT2) &&
(*Harmonic_Block == 0))
{
if (*Idiff_A > ((*Ibias_A) * (*SLP2)))
*Output = 1;
else
*Output=0;
}
4. Simulation results and discussion
The main goal of the simulation is either to obtain or
calculate waveforms such as currents on both sides of
transformer, TAP position, voltage at bus C41, IDIFF, IBIAS,
trip signal, and harmonic block signal during normal/fault
conditions for analysis of the behavior of relay.
4.1. Case.1. Normal Condition
When the transformer is operating normally, TAP
position is 9 and the resulting voltage at bus C41 is
0.99pu. The differential currents in all the phases
(IDIFF = 0.028) are well below pick up value O87P = 0.3,
IBIAS = 1.35 and the relay does not issue any trip signal.
Figure 7 shows IDIFF and IBIAS in any one phase (phase
A) and relay output.
Figure 7. TAP position at 9
As the transformer taps further from the balance
position (9), i.e. TAP position is 18 and voltage at bus C41
is 0.855pu, so the magnitude of the different current
increases IDIFF = 0.14, IBIAS = 1.08. However, the
differential current is still smaller than 0.2, the relay will
not trip (shown in Figure 8).
Figure 8. TAP position at 18
There are other ways to increase IDIFF by the CT errors.
It makes secondary current on two sides, not equation
under healthy conditions; for example a 15VA - 5P20 CT
has a guaranteed error of less than ± 5% when it is
subjected to 20 times its nominal current and delivers into
its nominal load (15 VA to In). At TAP = 9, current in HV
side is (CT error +5%) and current in LV side is (CT error
-5%), then IDIFF = 0.11, IBIAS = 1.35. Relay does not issue
any trip signal as shown in Figure 9.
Figure 9. TAP position at 9, CTHV error +5%, CTLV error -5%
At TAP = 9, the transformer is energized from the HV
side, magnetizing currents appear due to its core
magnetization and saturation. Figure 10 shows the waveform
of a magnetizing inrush current with transformer energized at
0.1s. The IDIFF is = 0.88, IBIAS = 0.44 but the relay does not
issue any trip signal because harmonic blocking signal is = 1.
12 Le Kim Hung, Vu Phan Huan
Figure 10. Harmonic block for energization condition
4.2. Case.2. Fault Condition
There are various types of faults, such as single phase to
ground, double phase, double phase-to-ground, and three
phases. If a fault is detected, i.e. the start signals will be set
by the differential protection (the measured IDIFF > O87P),
and at the same time the internal/ external fault discriminator
will determine the relative phase angle between them.
Figure 11. Internal fault at phase A to ground
For an internal AG fault is performed on F1, it is located
within the differential protection zone. Therefore, the fault
currents will flow out from the faulty power transformer on
both sides. The fault currents on the HV and LV sides will
have the same direction as shown in Figure 11. In the figure
immediately after the fault is applied, we can observe that
fault current in HV side is increased enormously,
IDIFF is = 4.35, IBIAS = 3.1 and the trip signal occurs at 0.12s.
Figure 12. External fault at phase AB
For an external AB fault is performed on F2, it is
located in the LV side of the transformer model. The fault
current contributions from the HV and LV side are
180 degrees out of phase as shown in Figure 12.
IDIFF is = 0.106, IBIAS is = 3.76 and relay does not trip.
Reviews: By using numerical relays, problems like CT
ratio mismatches and phase shift compensation can be
solved mathematically in the software of the relay. Besides,
the test point results of relay SEL387 (shown in Figure 4b)
demonstrate the stable operation during cases of normal
conditions (CT error, the change in tap position of a power
transformer, and magnetizing inrushes), external fault and
higher sensitivity during internal faults.
5. Summary
This paper provides a detailed description of a
transformer different protection function based on a
two-slope characteristic. It also provides valuable tips on
how to guide the setting calculation and troubleshooting
process. Furthermore, the power system model simulates
numerous test cases for an existing power transformer of
Lang Co Substation, Viet Nam using Matlab/Simulink
software package. These test cases save time by
immediately indicating whether the issue has occurred on
the SEL387. As a result, protection engineers can easily
analyze the mis-operation to determine the root cause and
can fulfill very demanding requirements set by power
utilities.
REFERENCES
[1] Sandro Gianny Aquiles Perez, “Modeling relays for power system
protection studies”, the Degree of Doctor of Philosophy in the
Department of Electrical Engineering University of Saskatchewan
Saskatoon, Saskatchewan Canada, July 2006.
[2] Casper Labuschagne and Normann Fischer, "Relay-Assisted
Commissioning", 59th Annual Conference for Protective Relay
Engineers College Station, Texas, April 4–6, 2006.
[3] SEL, “SEL-387 Relay Current Differential Instruction Manual”,
2010.
[4] Zoran Gajić, “Differential Protection for Arbitrary Three-Phase
Power Transformers”, Doctoral Dissertation Department of
Industrial Electrical Engineering and Automation, Lund University,
SWEDEN, 2008.
[5] M. Tanveer Ahmad, “Differential Protection of Transformer using
Harmonic Restraint Circuitry”, The 12th GCC Cigre International
Conference, Doha, Qatar, 8-10 November, 2016.
[6] Decision No. A3-06-2015/LCO110 by the Central Region Load
Dispatch Centre of Vietnam.
(The Board of Editors received the paper on 31/01/2018, its review was completed on 26/02/2018)
Các file đính kèm theo tài liệu này:
- performance_analysis_and_assessment_of_a_transformer_differe.pdf